LEED v5 IEQ Credit Calculator
Total Points: 0 / 10
Option 1: Continuous Indoor Air Monitoring (1–10 points)
Continuously measure indoor air parameters to earn points based on benchmark performance.
CO2
PM2.5
TVOC
Option 2: Targeted One-time Air testing (1–3 points)
Perform one-time tests and meet the minimum concentration limits for listed parameters.
Option 3: Targeted One-Time Individual Volatile Organic Compounds Testing (2 points)
Test for and meet the concentration limits for a list of individual VOCs.
- TVOC [Investigate and take corrective action if levels exceed 500 µg/m³]
- Formaldehyde [20 µg/m³]
- Acetaldehyde [140 µg/m³]
- Benzene [3 µg/m³]
- Hexane (n-) [7,000 µg/m³]
- Naphthalene [9 µg/m³]
- Phenol [200 µg/m³]
- Styrene [900 µg/m³]
- Tetrachloroethylene [35 µg/m³]
- Toluene [300 µg/m³]
- Vinyl acetate [200 µg/m³]
- Dichlorobenzene (1,4-) [800 µg/m³]
- Xylenes – total [700 µg/m³]